Counter Module 750-404 5
:$*2,26<67(0
Counter with enable input 750-404/000-001
Technical description:
The counter module also can be ordered as counter with enable input (750-404/000-
001).
The counter begins processing with pulses at the CLOCK input. The changes from 0 V
to 24 V are counted.
The counter counts down if the input U/D is set at 24 V. With an open circuit input or 0
V the counter counts up.
The data format of the module is 4 bytes data and a control/status byte. The module is a
32 Bit counter. The ID Code os 180 (0xB4). The format of input and output data is the
same as 750-404.
The counter module is able to run with all WAGOÇI/OÇSYSTEM bus-couplers
(except for the economy type).